<?xml version="1.0" encoding="UTF-8"?>
<zabbix_export>
    <version>5.2</version>
    <date>2026-10-07T00:00:00Z</date>
    <groups>
        <group>
            <name>Templates/MiRCA</name>
        </group>
    </groups>
    <templates>
        <template>
            <template>MiRCA Port 1 Victron VE.Bus</template>
            <name>MiRCA Port 1 Victron VE.Bus</name>
            <description>MiRCA serial port 1 running the 'Victron VE.Bus' protocol (protocol id 1). SNMP v2c over the Ethernet interface, tree .1.3.6.1.4.1.2021.13.16.4.2.1 (doc/ports.md). Link 'MiRCA Device' too. Victron Multiplus / Quattro, passive listening on VE.Bus.</description>
            <groups>
                <group>
                    <name>Templates/MiRCA</name>
                </group>
            </groups>
            <applications>
                <application>
                    <name>Port 1</name>
                </application>
                <application>
                    <name>Inverter</name>
                </application>
            </applications>
            <items>
                <item>
                    <name>Port 1: protocol</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.1</snmp_oid>
                    <key>mirca.p1.protocol</key>
                    <delay>{$MIRCA.INTERVAL.SLOW}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>UNSIGNED</value_type>
                    <description>Protocol configured on the port</description>
                    <applications>
                        <application>
                            <name>Port 1</name>
                        </application>
                    </applications>
                    <valuemap>
                        <name>MiRCA protocol</name>
                    </valuemap>
                </item>
                <item>
                    <name>Port 1: online</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.2</snmp_oid>
                    <key>mirca.p1.online</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>UNSIGNED</value_type>
                    <description>1 while the device answers. All values read 0 while it is offline.</description>
                    <applications>
                        <application>
                            <name>Port 1</name>
                        </application>
                    </applications>
                    <valuemap>
                        <name>MiRCA online</name>
                    </valuemap>
                </item>
                <item>
                    <name>Port 1: seconds since last reply</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.3</snmp_oid>
                    <key>mirca.p1.age</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>s</units>
                    <description>-1: no reply since boot</description>
                    <applications>
                        <application>
                            <name>Port 1</name>
                        </application>
                    </applications>
                </item>
                <item>
                    <name>Port 1: DC voltage</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.30</snmp_oid>
                    <key>mirca.p1.dc_voltage</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>V</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 1: DC current</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.31</snmp_oid>
                    <key>mirca.p1.dc_current</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>A</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 1: AC frequency</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.32</snmp_oid>
                    <key>mirca.p1.ac_frequency</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>Hz</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 1: power factor</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.1.33</snmp_oid>
                    <key>mirca.p1.power_factor</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 1: DC power (calculated)</name>
                    <type>CALCULATED</type>
                    <key>mirca.p1.dc_power.calc</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>W</units>
                    <params>last(mirca.p1.dc_voltage)*last(mirca.p1.dc_current)</params>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                </item>
            </items>
            <macros>
                <macro>
                    <macro>{$MIRCA.INTERVAL}</macro>
                    <value>30s</value>
                    <description>Polling interval of live values</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.INTERVAL.SLOW}</macro>
                    <value>5m</value>
                    <description>Polling interval of slowly changing values (capacity, cycles, energy counters)</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.OFFLINE.TIME}</macro>
                    <value>5m</value>
                    <description>How long the device may stay silent before a problem is raised</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.AC.FREQ.MIN}</macro>
                    <value>49</value>
                    <description>AC frequency low threshold, Hz</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.AC.FREQ.MAX}</macro>
                    <value>51</value>
                    <description>AC frequency high threshold, Hz</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.DC.VOLTAGE.MIN}</macro>
                    <value>0</value>
                    <description>DC voltage low threshold, V (0 = disabled). Per port: {$MIRCA.DC.VOLTAGE.MIN:"p1"}</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.DC.VOLTAGE.MAX}</macro>
                    <value>0</value>
                    <description>DC voltage high threshold, V (0 = disabled). Per port: {$MIRCA.DC.VOLTAGE.MAX:"p1"}</description>
                </macro>
            </macros>
        </template>
        <template>
            <template>MiRCA Port 2 Victron VE.Bus</template>
            <name>MiRCA Port 2 Victron VE.Bus</name>
            <description>MiRCA serial port 2 running the 'Victron VE.Bus' protocol (protocol id 1). SNMP v2c over the Ethernet interface, tree .1.3.6.1.4.1.2021.13.16.4.2.2 (doc/ports.md). Link 'MiRCA Device' too. Victron Multiplus / Quattro, passive listening on VE.Bus.</description>
            <groups>
                <group>
                    <name>Templates/MiRCA</name>
                </group>
            </groups>
            <applications>
                <application>
                    <name>Port 2</name>
                </application>
                <application>
                    <name>Inverter</name>
                </application>
            </applications>
            <items>
                <item>
                    <name>Port 2: protocol</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.1</snmp_oid>
                    <key>mirca.p2.protocol</key>
                    <delay>{$MIRCA.INTERVAL.SLOW}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>UNSIGNED</value_type>
                    <description>Protocol configured on the port</description>
                    <applications>
                        <application>
                            <name>Port 2</name>
                        </application>
                    </applications>
                    <valuemap>
                        <name>MiRCA protocol</name>
                    </valuemap>
                </item>
                <item>
                    <name>Port 2: online</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.2</snmp_oid>
                    <key>mirca.p2.online</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>UNSIGNED</value_type>
                    <description>1 while the device answers. All values read 0 while it is offline.</description>
                    <applications>
                        <application>
                            <name>Port 2</name>
                        </application>
                    </applications>
                    <valuemap>
                        <name>MiRCA online</name>
                    </valuemap>
                </item>
                <item>
                    <name>Port 2: seconds since last reply</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.3</snmp_oid>
                    <key>mirca.p2.age</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>s</units>
                    <description>-1: no reply since boot</description>
                    <applications>
                        <application>
                            <name>Port 2</name>
                        </application>
                    </applications>
                </item>
                <item>
                    <name>Port 2: DC voltage</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.30</snmp_oid>
                    <key>mirca.p2.dc_voltage</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>V</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 2: DC current</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.31</snmp_oid>
                    <key>mirca.p2.dc_current</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>A</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 2: AC frequency</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.32</snmp_oid>
                    <key>mirca.p2.ac_frequency</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>Hz</units>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 2: power factor</name>
                    <type>SNMP_AGENT</type>
                    <snmp_oid>1.3.6.1.4.1.2021.13.16.4.2.2.33</snmp_oid>
                    <key>mirca.p2.power_factor</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                    <preprocessing>
                        <step>
                            <type>MULTIPLIER</type>
                            <parameters>
                                <parameter>0.01</parameter>
                            </parameters>
                        </step>
                    </preprocessing>
                </item>
                <item>
                    <name>Port 2: DC power (calculated)</name>
                    <type>CALCULATED</type>
                    <key>mirca.p2.dc_power.calc</key>
                    <delay>{$MIRCA.INTERVAL}</delay>
                    <history>14d</history>
                    <trends>365d</trends>
                    <value_type>FLOAT</value_type>
                    <units>W</units>
                    <params>last(mirca.p2.dc_voltage)*last(mirca.p2.dc_current)</params>
                    <applications>
                        <application>
                            <name>Inverter</name>
                        </application>
                    </applications>
                </item>
            </items>
            <macros>
                <macro>
                    <macro>{$MIRCA.INTERVAL}</macro>
                    <value>30s</value>
                    <description>Polling interval of live values</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.INTERVAL.SLOW}</macro>
                    <value>5m</value>
                    <description>Polling interval of slowly changing values (capacity, cycles, energy counters)</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.OFFLINE.TIME}</macro>
                    <value>5m</value>
                    <description>How long the device may stay silent before a problem is raised</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.AC.FREQ.MIN}</macro>
                    <value>49</value>
                    <description>AC frequency low threshold, Hz</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.AC.FREQ.MAX}</macro>
                    <value>51</value>
                    <description>AC frequency high threshold, Hz</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.DC.VOLTAGE.MIN}</macro>
                    <value>0</value>
                    <description>DC voltage low threshold, V (0 = disabled). Per port: {$MIRCA.DC.VOLTAGE.MIN:"p1"}</description>
                </macro>
                <macro>
                    <macro>{$MIRCA.DC.VOLTAGE.MAX}</macro>
                    <value>0</value>
                    <description>DC voltage high threshold, V (0 = disabled). Per port: {$MIRCA.DC.VOLTAGE.MAX:"p1"}</description>
                </macro>
            </macros>
        </template>
    </templates>
    <triggers>
        <trigger>
            <expression>{MiRCA Port 1 Victron VE.Bus:mirca.p1.protocol.last()}&lt;&gt;1</expression>
            <name>Port 1: protocol is not Victron VE.Bus (template does not match port settings)</name>
            <priority>WARNING</priority>
            <description>The port runs protocol {ITEM.LASTVALUE}. Change the port settings or link another template.</description>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 1 Victron VE.Bus:mirca.p1.online.max({$MIRCA.OFFLINE.TIME})}=0 and {MiRCA Port 1 Victron VE.Bus:mirca.p1.protocol.last()}=1</expression>
            <name>Port 1: Victron VE.Bus not responding</name>
            <priority>AVERAGE</priority>
            <description>No valid reply from the device for {$MIRCA.OFFLINE.TIME}. Check wiring, interface module, baud rate and device address.</description>
        </trigger>
        <trigger>
            <expression>({MiRCA Port 1 Victron VE.Bus:mirca.p1.ac_frequency.max(2m)}&lt;{$MIRCA.AC.FREQ.MIN} or {MiRCA Port 1 Victron VE.Bus:mirca.p1.ac_frequency.min(2m)}&gt;{$MIRCA.AC.FREQ.MAX}) and {MiRCA Port 1 Victron VE.Bus:mirca.p1.ac_frequency.last()}&gt;0 and {MiRCA Port 1 Victron VE.Bus:mirca.p1.online.last()}=1</expression>
            <name>Port 1: AC frequency out of range ({ITEM.LASTVALUE1})</name>
            <priority>AVERAGE</priority>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 1 Victron VE.Bus:mirca.p1.dc_voltage.max(5m)}&lt;{$MIRCA.DC.VOLTAGE.MIN:"p1"} and {$MIRCA.DC.VOLTAGE.MIN:"p1"}&gt;0 and {MiRCA Port 1 Victron VE.Bus:mirca.p1.online.last()}=1</expression>
            <name>Port 1: DC voltage is low (&lt;{$MIRCA.DC.VOLTAGE.MIN:"p1"}V)</name>
            <priority>AVERAGE</priority>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 1 Victron VE.Bus:mirca.p1.dc_voltage.min(5m)}&gt;{$MIRCA.DC.VOLTAGE.MAX:"p1"} and {$MIRCA.DC.VOLTAGE.MAX:"p1"}&gt;0 and {MiRCA Port 1 Victron VE.Bus:mirca.p1.online.last()}=1</expression>
            <name>Port 1: DC voltage is high (&gt;{$MIRCA.DC.VOLTAGE.MAX:"p1"}V)</name>
            <priority>AVERAGE</priority>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 2 Victron VE.Bus:mirca.p2.protocol.last()}&lt;&gt;1</expression>
            <name>Port 2: protocol is not Victron VE.Bus (template does not match port settings)</name>
            <priority>WARNING</priority>
            <description>The port runs protocol {ITEM.LASTVALUE}. Change the port settings or link another template.</description>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 2 Victron VE.Bus:mirca.p2.online.max({$MIRCA.OFFLINE.TIME})}=0 and {MiRCA Port 2 Victron VE.Bus:mirca.p2.protocol.last()}=1</expression>
            <name>Port 2: Victron VE.Bus not responding</name>
            <priority>AVERAGE</priority>
            <description>No valid reply from the device for {$MIRCA.OFFLINE.TIME}. Check wiring, interface module, baud rate and device address.</description>
        </trigger>
        <trigger>
            <expression>({MiRCA Port 2 Victron VE.Bus:mirca.p2.ac_frequency.max(2m)}&lt;{$MIRCA.AC.FREQ.MIN} or {MiRCA Port 2 Victron VE.Bus:mirca.p2.ac_frequency.min(2m)}&gt;{$MIRCA.AC.FREQ.MAX}) and {MiRCA Port 2 Victron VE.Bus:mirca.p2.ac_frequency.last()}&gt;0 and {MiRCA Port 2 Victron VE.Bus:mirca.p2.online.last()}=1</expression>
            <name>Port 2: AC frequency out of range ({ITEM.LASTVALUE1})</name>
            <priority>AVERAGE</priority>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 2 Victron VE.Bus:mirca.p2.dc_voltage.max(5m)}&lt;{$MIRCA.DC.VOLTAGE.MIN:"p2"} and {$MIRCA.DC.VOLTAGE.MIN:"p2"}&gt;0 and {MiRCA Port 2 Victron VE.Bus:mirca.p2.online.last()}=1</expression>
            <name>Port 2: DC voltage is low (&lt;{$MIRCA.DC.VOLTAGE.MIN:"p2"}V)</name>
            <priority>AVERAGE</priority>
        </trigger>
        <trigger>
            <expression>{MiRCA Port 2 Victron VE.Bus:mirca.p2.dc_voltage.min(5m)}&gt;{$MIRCA.DC.VOLTAGE.MAX:"p2"} and {$MIRCA.DC.VOLTAGE.MAX:"p2"}&gt;0 and {MiRCA Port 2 Victron VE.Bus:mirca.p2.online.last()}=1</expression>
            <name>Port 2: DC voltage is high (&gt;{$MIRCA.DC.VOLTAGE.MAX:"p2"}V)</name>
            <priority>AVERAGE</priority>
        </trigger>
    </triggers>
    <graphs>
        <graph>
            <name>Port 1: DC voltage and current</name>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <color>1A7C11</color>
                    <item>
                        <host>MiRCA Port 1 Victron VE.Bus</host>
                        <key>mirca.p1.dc_voltage</key>
                    </item>
                </graph_item>
                <graph_item>
                    <sortorder>1</sortorder>
                    <color>F63100</color>
                    <yaxisside>RIGHT</yaxisside>
                    <item>
                        <host>MiRCA Port 1 Victron VE.Bus</host>
                        <key>mirca.p1.dc_current</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Port 1: AC frequency</name>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <color>1A7C11</color>
                    <item>
                        <host>MiRCA Port 1 Victron VE.Bus</host>
                        <key>mirca.p1.ac_frequency</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Port 2: DC voltage and current</name>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <color>1A7C11</color>
                    <item>
                        <host>MiRCA Port 2 Victron VE.Bus</host>
                        <key>mirca.p2.dc_voltage</key>
                    </item>
                </graph_item>
                <graph_item>
                    <sortorder>1</sortorder>
                    <color>F63100</color>
                    <yaxisside>RIGHT</yaxisside>
                    <item>
                        <host>MiRCA Port 2 Victron VE.Bus</host>
                        <key>mirca.p2.dc_current</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
        <graph>
            <name>Port 2: AC frequency</name>
            <graph_items>
                <graph_item>
                    <sortorder>0</sortorder>
                    <color>1A7C11</color>
                    <item>
                        <host>MiRCA Port 2 Victron VE.Bus</host>
                        <key>mirca.p2.ac_frequency</key>
                    </item>
                </graph_item>
            </graph_items>
        </graph>
    </graphs>
    <value_maps>
        <value_map>
            <name>MiRCA online</name>
            <mappings>
                <mapping>
                    <value>0</value>
                    <newvalue>Offline</newvalue>
                </mapping>
                <mapping>
                    <value>1</value>
                    <newvalue>Online</newvalue>
                </mapping>
            </mappings>
        </value_map>
        <value_map>
            <name>MiRCA protocol</name>
            <mappings>
                <mapping>
                    <value>0</value>
                    <newvalue>Off</newvalue>
                </mapping>
                <mapping>
                    <value>1</value>
                    <newvalue>Victron VE.Bus</newvalue>
                </mapping>
                <mapping>
                    <value>2</value>
                    <newvalue>JK BMS 4G-GPS</newvalue>
                </mapping>
                <mapping>
                    <value>3</value>
                    <newvalue>PACE BMS</newvalue>
                </mapping>
                <mapping>
                    <value>4</value>
                    <newvalue>JBD BMS</newvalue>
                </mapping>
                <mapping>
                    <value>5</value>
                    <newvalue>JK BMS Modbus</newvalue>
                </mapping>
                <mapping>
                    <value>6</value>
                    <newvalue>Deye inverter Modbus</newvalue>
                </mapping>
                <mapping>
                    <value>7</value>
                    <newvalue>Serial capture</newvalue>
                </mapping>
                <mapping>
                    <value>8</value>
                    <newvalue>JK BMS parallel bus</newvalue>
                </mapping>
            </mappings>
        </value_map>
    </value_maps>
</zabbix_export>